Most of what you need to know will be below.


DHF-TS-011-code-of-practice-for-powered-gates-&-barriers---version-3-2018.pdf

Gates not closing?

Put dip switch 8 on (up) and see if the gates then close

As dip switch 8 disables photocells ...


Gates not closing?

Put dipswitch 8 on (up) and see if the gates then close

As dipswitch 8 disables photocells ...


Or is it safety bumpstrips not working and keeping the gates open ?

Put the 1st dipswitch

in the row of 4 dipswitches to off then put a

link between 23 and 25 if the gate closes

the fault is with the safety bump strips


You need to do this as when 1 is on it's looking for an 8k2 resistore !!


Trouble shooting

Dip switch 1,2,3 down, 4,5,6,7,8,up 9,10 down
Dip 1,2,3,4, down if new f4 plus

IF YOU HAVE SW15 LINK REMOVE! (8K2 IF ON)
Link out 23 & 25 (stop)
Take anything out of 23 and 19
Put a bit of cable in 19 and tap it on 13 or press programmed fob should start the motors!
will start the gates!!

Below Are The Control Manuals For Gibidi 

NEW****F4 CONTROL PANEL*****2020***

AIC6564_F4_IT_UK_FR_ES_NL_Rev1.pdf

BA230 Control Panel

AIC5012BA230ITUK rev 01.pdf
AS05550manual BA230 old firmware.pdf
AIC6493_BA230_rev00 old old .. .pdf

The old BA230 has a molded in live nutral and double earth power supply input on the control board. The new version you can unplug the power supply from the control board

The old version you can't add the time clock 

Most asked about BA230 is


How do I attach a time clock to keep gates open?


On control panel go to E9 and turn to 4 then

connect time clock to 28 and 32 NO connection and when it switches to NC gates open


How do I attach safety bump strips?


On control panel go to C9 and turn to 2 for 8k2 or 3 for NC

then connect the strips to 29 and 32  


Gates won't close?


Have a look at photocells.. see if working ok..

Have a look at safety strips if fitted ..

Or short out  22, (stop) 27 (photo2) 29 (safty nc)

and 31 (photo1) all to 32 common gates should close


Dont forget to turn C3 to 1... That turns off the 3 seconds :)


BA100 Control Panel

AIC4978_BA100_IT_UK_Rev2 gibidi.pdf

BA24 Control Panel

ba24 gibidi 1.pdf
ba24 gibidi 1.pdf

F12 Control Panel

AS04000F12 F12 old version .pdf
AIC2011_F12E_IT_UK_ES_NL_F_D_Rev02.pdf
AIC1081_F12RALLY_rev00.pdf

BR24 Control Panel

AIC8690_BR24_IT-UK_Rev0 GIBIDI.pdf
AIC5001_BR24_IT-UK immagini REV2 GIBIDI.pdf

BE24 Control Panel

AIC4918_BE24_Rev1 GIBIDI.pdf
AIC4923_BE24_AS05870_IT_UK_FR_ES GIBIDI.pdf

PC200 Control Panel

AIC8792_Rev1_PC_200_TESTO_IT_UK.pdf
3513techdoc.pdf
kuda_pc200_control_panel_as06050.pdf

SC230E Control Panel

AIC0003_SC230E_IT-UK-FR-ES_Rev1.pdf

SC230 Control Panel

3595-techdoc2016sc230with8k2.pdf

If fitting the unit the 8k2 need to be in place or in line for the control panel for it to work
DON'T put a link in stop to com and the 8k2 as the unit wont work
As the unit needs to see the 8k2!!! same for the costa (safety) and com
so as they are or in line

Dip switch 9 on if you have a newer unit with a RPM SENSOR!

Also the unit 2 dip switches at the back of the control panel by the receiver unit plug in this gets missed TURN THE BREAK ON ! (IF ITS NEEDED!)

Older SC230 Control Panels

sc230gibidipanelsliding.pdf
AIC7081_SC230_rev01.pdf

SE24E Control Panel 

AIC8982_SE24_IT_UK_Rev1 GIBIDI.pdf

New SC24 Control Panel

AIC8745_SC24_rev0 it_uk GIBIDI 8K2.pdf

If fitting the unit the 8k2 need to be in place or in line for the control panel for it to work 
DON'T put a link in stop to com and the 8k2 as the unit wont work 
as the unit needs to see the 8k2!!! same for the costa (safety) and com
so as they are or in line

Older SC24 Control Panels

gibidi24vsc24slidinggatepanel.pdf

F3PLUS Control Panel

f3plus gibidi.pdf

PLUS 2 A Control Panel

gibidi_plus2.pdf

PLUS 2 Control Panel

gibidi_plus2.pdf

PLUS 1 Control Panel

AIC2990PLUS1Brev03.pdf

Garage Door Control Panels

AIC4220_REV05_GECO 60-80.pdf
geco trainer amendment (1).PDF

Gibidi Analogic Taimen 24v

AIC8185_TAIMEN IT-UK_Rev 0.pdf

Gibidi Digital Taimen 24v

AIC8211_TAIMEN IT-UK_Rev 1.pdf
AIC8800_TAIMEN_BATTERIE_Rev 1.pdf

Gibidi Taimen 

Gibidi Receiver Units 

AIC4016_DRS4331_Rev0 1 way receiver unit gibidi.pdf
AIC6503_DOMINO_DRS_rev03 plig in receiver unit gibidi.pdf
AIC6480_istr_scheda_ricevente_2810_rev3 4 way stand alone receiver unit gibidi.pdf

Gibidi Photocells

AIC8999_DCF180 gibidi.pdf
AIC6482_DCF180D_impaginato_rev1 gibidi.pdf
AIC6555_DGF100200_Rev00 sq gibidi.pdf

Gibidi Roller Shutter Control Unit 230V

AIC8301_REV1 gibidi roller 230v control panel.pdf